ABB

1SAM340010R1014

Product type: MS132-25KT

MS132-25KT Circuit-breaker for primary transformer protection,Trip Class 10

Description

The circuit breaker for transformer protection MS132-25KT is a compact 45 mm width device designed to protect control transformers on the primary side. This device has a rated operational current of Ie = 25 A with Push-In Spring terminals. It allows fuseless protection against overload and short-circuit. The short-circuit current setting is fixed to 20 times the rated operational current to handle the high inrush current generated by transformers. The device allows manually connect and disconnect the transformer from the mains thanks of its built-in disconnection function. The circuit breaker for transformer protection offers a rated service short-circuit breaking capacity of Ics = 50 kA at 400 VAC and trip class 10. Further features are temperature compensation, trip-free mechanism, rotary handle with a clear switch position indication and short circuit trip indicator. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips and terminal spacers are available as accessory.
  • Low Voltage Products and Systems
  • Control Products
  • Manual Motor Starters
  • Manual Motor Starters for Special Use
Contact Person
Thomas Hoffmann
+49 305 201 4443 ext. 1
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: ca. 1-2 Days
Delivery Time: By Agreement
Delivery Terms: FCA Berlin
Infoindividually for each client according to INCOM TERMS 2022
  • ZWOD Vertriebs und Logistik GmbH specializes in hard-to-find parts. Please send request a quote and save on 1SAM340010R1014.
  • ZWOD Vertriebs und Logistik GmbH carries 226480 items from ABB.
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.316 KG / psc.
Commodity number85362010
Country of origin
Dimensions (WxHxD)45x112x87 mm
EAN code4013614535246
Product group
eclassV11.0 : 27370409
etim 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
etim 6EC000228 - Power circuit-breaker for trafo/generator/installation prot.
etim 7EC000228 - Power circuit-breaker for trafo/generator/installation protection
etim 8EC000228 - Power circuit-breaker for trafo/generator/installation protection
unspsc39121601
standardsIEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1
power lossat Rated Operating Conditions per Pole 1.2 ... 1.9 W
rohs statusFollowing EU Directive 2011/65/EU
actuator typeRotary Handle
setting range20 ... 25 A
terminal typePush-in Spring Terminals
kc certificatehttps://library.abb.com/d/1SAA963002-1502
cqc certificatehttps://library.abb.com/d/CQC2017010307034621
cul certificatehttps://library.abb.com/d/cUL_E137861
cur certificatehttps://library.abb.com/d/cUL_E137861
marketing videohttps://library.abb.com/d/9AKK107991A4712, https://library.abb.com/d/2CDC131153V0201
number of poles3
pollution degree3
rmrs certificatehttps://library.abb.com/d/1SAA918000-0704
rohs informationhttps://library.abb.com/d/1SAD938508-0188
culus certificatehttps://library.abb.com/d/cUL_E137861
locked rotor amps(120 V AC) Single Phase 144 A(220 ... 240 V AC) Single Phase 144 A
mounting position1 ... 6
e-number (finland)3709090
i2t characteristichttps://library.abb.com/d/1SAM300517F0001
rated frequency (f)Main Circuit 50 HzMain Circuit 60 Hz
degree of protectionHousing IP20Main Circuit Terminals IP20
mounting on din railTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
electrical durability50000 cycle
mechanical durability100000 cycle
wire stripping lengthMain Circuit 12 mm
ambient air temperatureAround the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C
full load amps motor use(120 V AC) Single Phase 24 A(220 ... 240 V AC) Single Phase 17 A
horsepower rating ul/csa(120 V AC) Single Phase 2 Hp(220 ... 240 V AC) Single Phase 3 Hp
environmental informationhttps://library.abb.com/d/1SAC200049H0009
minimum mounting distanceElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 9 mmOther Device Same Type, Vertical 150 mm
rated operational voltageMain Circuit 690 V AC
object classification codeF
contact position indicationON / OFF / TRIP
rated insulation voltage (ui)690 V
declaration of conformity - cehttps://library.abb.com/d/1SAD101100-3404
rated operational current (ie)25 A
declaration of conformity - ccchttps://library.abb.com/d/2020980307004600
connecting capacity main circuitFlexible with Ferrule 1/2x 0.5 ... 4 mm2Flexible with Insulated Ferrule 1x 0.5 ... 4 mm2Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm2Flexible 1/2x 0.75 ... 4 mm2Solid 1/2x 1 ... 2.5 mm2Stranded 1/2x 1 ... 6 mm2
declaration of conformity - ukcahttps://library.abb.com/d/1SAD201100-3404
maximum operating voltage ul/csaMain Circuit 600 V AC
data sheet, technical informationhttps://library.abb.com/d/2CDC131058D0201
time-current characteristic curvehttps://library.abb.com/d/1SAM300535F0014
idea granular category code (igcc)4813 >> Circuit breakers
short-circuit current rating (sccr)Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA
ambient air temperature compensationYes
maximum operating altitude permissible2000 m
rated impulse withstand voltage (uimp)Main Circuit 6 kV
connecting capacity main circuit ul/csaStranded 1/2x 18-10 AWGStranded 1x 8 AWG
resistance to shock acc. to iec 60068-2-2711 ms Pulse 25g
conventional free-air thermal current (ith)Main Circuit 25 A
resistance to vibrations acc. to iec 60068-2-65g / 3 ... 150 Hz
rated service short-circuit breaking capacity (ics)(230 V AC) 50 kA(400 V AC) 50 kA(440 V AC) 30 kA
rated ultimate short-circuit breaking capacity (icu)(400 V AC) 50 kA
rated instantaneous short-circuit current setting (ii)500 A