TF42-0.74 Thermal Overload Relay

Description

The TF42-0.74 thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP function and a trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Thermal Overload Relays
Contact Person
Thomas Hoffmann
+49 305 201 4443 ext. 1
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: ca. 1-2 Days
Delivery Time: By Agreement
Delivery Terms: FCA Berlin
Infoindividually for each client according to INCOM TERMS 2022
  • ZWOD Vertriebs und Logistik GmbH specializes in hard-to-find parts. Please send request a quote and save on 1SAZ721201R1021.
  • ZWOD Vertriebs und Logistik GmbH carries 226480 items from ABB.
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.13 KG / psc.
Commodity number85364900
Country of originDE
Dimensions (WxHxD)45x88.3x70.5 mm
EAN code4013614398032
Product groupSE
eclassV11.0 : 27371501
etim 4EC000106 - Thermal overload relay
etim 5EC000106 - Thermal overload relay
etim 6EC000106 - Thermal overload relay
etim 7EC000106 - Thermal overload relay
etim 8EC000106 - Thermal overload relay
unspsc39121520
standardsIEC/EN 60947-1IEC/EN 60947-4-1IEC/EN 60947-5-1UL 60947-1UL 60947-4-1
power lossat Rated Operating Conditions per Pole 1.1 ... 2.0 W
rohs statusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
suitable forAF09AF12AF16AF26AF30AF38
setting range0.55 ... 0.74 A
bv certificatehttps://library.abb.com/d/1SAA941001-0203
cb certificatehttps://library.abb.com/d/1SAA941009-2001
gl certificatehttps://library.abb.com/d/1SAA941007-0401
lr certificatehttps://library.abb.com/d/1SAA941001-0502
ul certificatehttps://library.abb.com/d/E48139-20090126
abs certificatehttps://library.abb.com/d/1SAA941001-0102
cqc certificatehttps://library.abb.com/d/CQC2011010309464423
eac certificatehttps://library.abb.com/d/1SAA941002-2701
number of poles3
atex certificatehttps://library.abb.com/d/1SAA941001-3901
pollution degree3
rina certificatehttps://library.abb.com/d/1SAA941000-0802
rmrs certificatehttps://library.abb.com/d/1SAA941000-0704
rohs informationhttps://library.abb.com/d/1SAD938513-0181
dimension diagramhttps://library.abb.com/d/1SAZ700405F0001
e-number (sweden)3211960
iecex certificatehttps://library.abb.com/d/1SAA941003-4001
tightening torqueAuxiliary Circuit 1 ... 1.5 N·mMain Circuit 1.5 ... 2.5 N·m
dnv gl certificatehttps://library.abb.com/d/1SAA941001-0302
e-number (finland)3706116
rated frequency (f)Auxiliary Circuit 50 HzAuxiliary Circuit 60 HzAuxiliary Circuit DCMain Circuit 50 HzMain Circuit 60 Hz
ampere rating ul/csa0.74 A
degree of protectionIP20
contact rating ul/csa(NC:) B600(NC:) Q600(NO:) Q600(NO:) D300
wire stripping lengthAuxiliary Circuit 9 mmMain Circuit 12 mm
ambient air temperatureOperation -25 ... +60 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C
recommended screw driverMain Circuit Pozidriv 2
tightening torque ul/csaAuxiliary Circuit 9 ... 13 in·lbMain Circuit 13 ... 22 in·lb
environmental informationhttps://library.abb.com/d/1SAC200057H0009
number of protected poles3
rated operational voltageAuxiliary Circuit 600 V AC/DCMain Circuit 690 V ACMain Circuit 600 V DC
object classification codeF
rated insulation voltage (ui)690 V
declaration of conformity - cehttps://library.abb.com/d/1SAD938513-0181
rated operational current (ie)0.74 A
declaration of conformity - ccchttps://library.abb.com/d/2020980304001788
number of auxiliary contacts nc1
number of auxiliary contacts no1
connecting capacity main circuitFlexible with Ferrule 1/2x 0.75 ... 4 mm2Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm2Flexible 1/2x 0.75 ... 4 mm2Rigid 1/2x 0.75 ... 4 mm2
declaration of conformity - ukcahttps://library.abb.com/d/1SAD938501-1181
maximum operating voltage ul/csaMain Circuit 600 V AC
data sheet, technical informationhttps://library.abb.com/d/2CDC106023D0201
time-current characteristic curvehttps://library.abb.com/d/1SAZ700506F0007
idea granular category code (igcc)5364 >> Overload relay
ambient air temperature compensationYes
rated operational current ac-15 (ie)(120 V) NC 3 A(120 V) NO 0.5 A(240 V) NC 3 A(240 V) NO 0.5 A(400 V) NC 0.75 A(400 V) NO 0.5 A(500 V) NC 0.75 A(500 V) NO 0.5 A
rated operational current dc-13 (ie)(125 V) NC 0.55 A(125 V) NO 0.55 A(24 V) NC 1.25 A(24 V) NO 1.25 A(250 V) NC 0.27 A(250 V) NO 0.27 A(500 V) NC 0.15 A(500 V) NO 0.15 A(60 V) NC 0.55 A(60 V) NO 0.55 A
connecting capacity auxiliary circuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm2Flexible 1/2x 0.75 ... 1 mm2Flexible 1/2x 1 ... 2.5 mm2Rigid 1/2x 0.75 ... 4 mm2
maximum operating altitude permissible2000 m
rated impulse withstand voltage (uimp)Auxiliary Circuit 6 kVMain Circuit 6 kV
connecting capacity main circuit ul/csaFlexible 1/2x 18-10 AWGStranded 1/2x 18-10 AWG
resistance to shock acc. to iec 60068-2-2711 ms Pulse 25g
conventional free-air thermal current (ith)Auxiliary Circuit NC 6 AAuxiliary Circuit NO 4 A
connecting capacity auxiliary circuit ul/csaFlexible 1/2x 18-12 AWGStranded 1/2x 18-12 AWG
resistance to vibrations acc. to iec 60068-2-65g / 3 ... 150 Hz