ABB

1SBH131001R8439

Product type: NFC33/11-84

NFC33/11-84 110V50Hz 110-120V60Hz Contactor Relay

Description

The NFC33/11-84 is a contactor relay with 8 auxiliary contacts (4 N.O including 1 leading contact + 4 N.C including 1 lagging contact) and screw terminals, used to switch auxiliary and control circuits. Within the AF platform, NFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 110 V AC 50 Hz / 110 ... 120 V AC 60 Hz). NFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Block Contactors
Contact Person
Thomas Hoffmann
+49 305 201 4443 ext. 1
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: ca. 1-2 Days
Delivery Time: By Agreement
Delivery Terms: FCA Berlin
Infoindividually for each client according to INCOM TERMS 2022
  • ZWOD Vertriebs und Logistik GmbH specializes in hard-to-find parts. Please send request a quote and save on 1SBH131001R8439.
  • ZWOD Vertriebs und Logistik GmbH carries 225191 items from ABB.
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.362 KG / psc.
Commodity number85364900
Country of origin
Dimensions (WxHxD)45x86x110.5 mm
EAN code3471523015517
Product groupSB
eclassV11.0 : 27371001
etim 7EC000196 - Contactor relay
etim 8EC000196 - Contactor relay
standardsIEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
operate timeBetween Coil De-energization and NC Contact Closing 9 ... 20 msBetween Coil De-energization and NO Contact Opening 4 ... 18 msBetween Coil Energization and NC Contact Opening 7 ... 21 msBetween Coil Energization and NO Contact Closing 10 ... 26 ms
terminal typeScrew Terminals
cb certificatehttps://library.abb.com/d/CB_SE-93051M2
ul certificatehttps://library.abb.com/d/UL_20191021-E312527_7_1
cqc certificatehttps://library.abb.com/d/CQC2019010303267993
rohs informationhttps://library.abb.com/d/1SBD251089E1000
climatic withstandCategory B according to IEC 60947-1 Annex Q
rated frequency (f)Auxiliary Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
degree of protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
mounting on din railTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
wire stripping lengthAuxiliary Circuit 10 mmControl Circuit 10 mm
ambient air temperatureClose to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... 60 °CNear Contactor for Operation in Free Air (Uc) -40 ... 70 °C
tightening torque ul/csaAuxiliary Circuit 11 in·lbControl Circuit 11 in·lb
rated operational voltageAuxiliary Circuit 690 V
number of main contacts nc0
number of main contacts no0
object classification codeK
rated insulation voltage (ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 Vacc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 Vacc. to UL/CSA 600 V
declaration of conformity - cehttps://library.abb.com/d/1SBD250026U1000
declaration of conformity - ccchttps://library.abb.com/d/2020980303000175
number of auxiliary contacts nc4
number of auxiliary contacts no4
declaration of conformity - ukcahttps://library.abb.com/d/1SBD250047U1000
data sheet, technical informationhttps://library.abb.com/d/1SBC100219C0201
mounting by screws (not supplied)2 x M4 screws placed diagonally
rated control circuit voltage (uc)50 Hz 110 V60 Hz 110 ... 120 V
connecting capacity control circuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm2Rigid 1/2x 1 ... 2.5 mm2
rated operational current ac-15 (ie)(500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A
rated operational current dc-13 (ie)(24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W(400 V) 0.15 A / 60 W(500 V) 0.13 A / 65 W(600 V) 0.1 A / 60 W
connecting capacity auxiliary circuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm2Rigid 1/2x 1 ... 2.5 mm2
maximum electrical switching frequency(AC-1) 0 cycles per hour(AC-15) 1200 cycles per hour(AC-2 / AC-4) 0 cycles per hour(AC-3) 0 cycles per hour(DC-13) 900 cycles per hour
maximum mechanical switching frequency6000 cycles per hour
maximum operating altitude permissibleWithout Derating 3000 m
rated impulse withstand voltage (uimp)6 kV
resistance to shock acc. to iec 60068-2-27Closed, Shock Direction: B1 25 gOpen, Shock Direction: B1 5 gShock Direction: A 30 gShock Direction: B2 15 gShock Direction: C1 25 g
conventional free-air thermal current (ith)acc. to IEC 60947-5-1, q = 40 °C 16 A
resistance to vibrations acc. to iec 60068-2-65 ... 300 Hz 4 g closed position / 2 g open position
rated short-time withstand current low voltage (icw)for 0.1 s 140 Afor 1 s 100 A

We use cookies

This website collects cookies to deliver better user experience. By using our website, you agree to the use of cookies.

Find out how we use cookies.

We’re sorry, our website no longer supports
For your security and a speedy zwod experience, please update your browser: