ABB

1SBH131001R8453

Product type: NFC53E-84

NFC53E-84 110V50Hz 110-120V60Hz Contactor Relay

Description

The NFC53E-84 is a contactor relay with 8 auxiliary contacts (5 N.O + 3 N.C) and screw terminals, used to switch auxiliary and control circuits. Within the AF platform, NFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 110 V AC 50 Hz / 110 ... 120 V AC 60 Hz). NFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Block Contactors
Contact Person
Thomas Hoffmann
+49 3091508245
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: ca. 1-2 Days
Delivery Time: By Agreement
Delivery Terms: FCA Berlin
Infoindividually for each client according to INCOM TERMS 2022
  • ZWOD Vertriebs und Logistik GmbH specializes in hard-to-find parts. Please send request a quote and save on 1SBH131001R8453.
  • ZWOD Vertriebs und Logistik GmbH carries 221565 items from ABB.
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.357 KG / psc.
Commodity number85364900
Country of origin
Dimensions (WxHxD)45x86x110.5 mm
EAN code3471523015548
Product groupSB
eclassV11.0 : 27371001
etim 7EC000196 - Contactor relay
etim 8EC000196 - Contactor relay
unspsc39121500
standardsIEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
operate timeBetween Coil De-energization and NC Contact Closing 9 ... 20 msBetween Coil De-energization and NO Contact Opening 4 ... 18 msBetween Coil Energization and NC Contact Opening 7 ... 21 msBetween Coil Energization and NO Contact Closing 10 ... 26 ms
terminal typeScrew Terminals
cb certificatehttps://library.abb.com/d/CB_SE-93051M2
ul certificatehttps://library.abb.com/d/UL_20191021-E312527_7_1
cqc certificatehttps://library.abb.com/d/CQC2019010303267993
rohs informationhttps://library.abb.com/d/1SBD251089E1000
climatic withstandCategory B according to IEC 60947-1 Annex Q
rated frequency (f)Auxiliary Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
degree of protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
mounting on din railTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
wire stripping lengthAuxiliary Circuit 10 mmControl Circuit 10 mm
ambient air temperatureClose to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... 60 °CNear Contactor for Operation in Free Air (Uc) -40 ... 70 °C
tightening torque ul/csaAuxiliary Circuit 11 in·lbControl Circuit 11 in·lb
rated operational voltageAuxiliary Circuit 690 V
object classification codeK
rated insulation voltage (ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 Vacc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 Vacc. to UL/CSA 600 V
declaration of conformity - cehttps://library.abb.com/d/1SBD250026U1000
declaration of conformity - ccchttps://library.abb.com/d/2020980303000175
number of auxiliary contacts nc3
number of auxiliary contacts no5
declaration of conformity - ukcahttps://library.abb.com/d/1SBD250047U1000
data sheet, technical informationhttps://library.abb.com/d/1SBC100219C0201
mounting by screws (not supplied)2 x M4 screws placed diagonally
rated control circuit voltage (uc)50 Hz 110 V60 Hz 110 ... 120 V
connecting capacity control circuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm2Rigid 1/2x 1 ... 2.5 mm2
rated operational current ac-15 (ie)(500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A
rated operational current dc-13 (ie)(24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W(400 V) 0.15 A / 60 W(500 V) 0.13 A / 65 W(600 V) 0.1 A / 60 W
connecting capacity auxiliary circuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Rigid 1/2x 1 ... 2.5 mm2
maximum electrical switching frequency(AC-1) 0 cycles per hour(AC-15) 1200 cycles per hour(AC-2 / AC-4) 0 cycles per hour(AC-3) 0 cycles per hour(DC-13) 900 cycles per hour
maximum mechanical switching frequency6000 cycles per hour
maximum operating altitude permissibleWithout Derating 3000 m
rated impulse withstand voltage (uimp)6 kV
resistance to shock acc. to iec 60068-2-27Closed, Shock Direction: B1 25 gOpen, Shock Direction: B1 5 gShock Direction: A 30 gShock Direction: B2 15 gShock Direction: C1 25 gShock Direction: C2 25 g
conventional free-air thermal current (ith)acc. to IEC 60947-5-1, q = 40 °C 16 A
resistance to vibrations acc. to iec 60068-2-65 ... 300 Hz 4 g closed position / 2 g open position
rated short-time withstand current low voltage (icw)for 0.1 s 140 Afor 1 s 100 A