Weight | 48 KG / psc. |
Commodity number | 85365080 |
Country of origin | FI |
Dimensions (WxHxD) | 400x306x309 mm |
EAN code | 6417019338538 |
Product group | FA |
eclass | V11.1 : 27371403 |
etim 5 | EC000216 - Switch disconnector |
etim 6 | EC000216 - Switch disconnector |
etim 7 | EC000216 - Switch disconnector |
etim 8 | EC000216 - Switch disconnector |
unspsc | 39122233 |
power loss | 29 W |
handle type | Handle and shaft not included |
rohs status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
handle color | Black |
mounting type | Base mounting |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
operating mode | Front operated |
number of poles | 3 |
transition type | Open |
pollution degree | 3 |
rohs information | https://library.abb.com/d/1SCC011020D0201 |
reach declaration | https://library.abb.com/d/1SCC011021D0201 |
degree of protection | Front IP20 |
distance between phases | Standard |
environmental information | https://library.abb.com/d/1SCC303050D0201 |
rated operational voltage | 1000 V |
object classification code | Q |
position of line terminals | Top In - Bottom Out, Bottom In - Top Out |
switches operating mechanism | Mechanism at the End of the Switch03 (Left Side) |
rated insulation voltage (ui) | 1000 V |
declaration of conformity - ce | https://library.abb.com/d/1SCC303016D0201 |
data sheet, technical information | https://library.abb.com/d/1SCC303003C0201 |
rated operational power ac-23a (pe) | (380 ... 415 V) 710 kW(500 V) 900 kW(690 V) 1200 kW |
rated operational current ac-21a (ie) | (380 ... 415 V) 1250 A(500 V) 1250 A(690 V) 1250 A |
rated operational current ac-22a (ie) | (380 ... 415 V) 1250 A(500 V) 1250 A(690 V) 1250 A |
rated operational current ac-23a (ie) | (380 ... 415 V) 1250 A(500 V) 1250 A(690 V) 1250 A |
rated operational current ac-31b (ie) | (380 ... 415 V) 1250 A |
rated operational current ac-33b (ie) | (380 ... 415 V) 1250 A |
rated impulse withstand voltage (uimp) | 12 kV |
conventional free-air thermal current (ith) | q = 40 °C 1250 A |
rated short-time withstand current low voltage (icw) | for 1 s 50 kiloampere rms |