ABB

1SCA102323R1001

Product type: OT400ESUR3TZ

OT400ESUR3TZ Safety switch

Description

Safety switch, 3-p. 415V AC23 400A, 220kW. Mounted auxiliary contact: 2NO1NC. Stainless steel enclosure. IP65. StainlessSteel Pistol handle. Interlocked cover. Defeatable interlocking. The enclosure and handle of the OT series is made of rigid acid proof steel, class AISI316L. The enclosure has a hinged door, with door lock. The cover is interlocked, and can not be opened when switch is on. The interlock function can be defeated for thermographing. The cover has also a gas pressure releaf function, to protect the user in case of internal arc. Suitable for outdoor and indoor use. The cable entries holes are prepared for cable flanges. The cable flanges (KOT61007 or KOT62296 (for EMC)) and the covers for the holes (KOT61008), have to be bought separately. The switch can be used in EMC applications, if EMC ring flanges are used. PE terminals and auxiliary contacts are included.
  • Low Voltage Products and Systems
  • Enclosed Switches
  • Enclosed Safety Switches
  • Enclosed Safety Switches
Contact Person
Thomas Hoffmann
+49 305 201 4443 ext. 1
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: ca. 1-2 Days
Delivery Time: By Agreement
Delivery Terms: FCA Berlin
Infoindividually for each client according to INCOM TERMS 2022
  • ZWOD Vertriebs und Logistik GmbH specializes in hard-to-find parts. Please send request a quote and save on 1SCA102323R1001.
  • ZWOD Vertriebs und Logistik GmbH carries 226480 items from ABB.
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight32.75 KG / psc.
Commodity number85363090
Country of originFI
Dimensions (WxHxD)400x800x230 mm
EAN code6417019371122
Product groupFA
eclassV11.1 : 27371403
etim 5EC000216 - Switch disconnector
etim 6EC000216 - Switch disconnector
etim 7EC000216 - Switch disconnector
etim 8EC000216 - Switch disconnector
standardsIEC 60947-1, -3
power lossat Rated Operating Conditions per Pole 10 W
handle typePistol handle
rohs statusFollowing EU Directive 2011/65/EU
handle colorStainless Steel
weee category4. Large Equipment (Any External Dimension More Than 50 cm)
number of poles3
pollution degree3
rohs informationhttps://library.abb.com/d/1SCC340025D2704
e-number (sweden)3135040
e-number (finland)3642118
enclosure materialStainless steel
mechanical drawingshttps://library.abb.com/d/OTRK804023PBL4R.stp
cable entry positionDown/Down
degree of protectionacc. to IEC 60529 IP65
cable outlets per sideBlank / 4xring-flange+ø25.5mm
impact resistance ratingHousing IK09
rated operational voltageMain Circuit 1000 V
mounted auxiliary contacts2 NO, 1 NC
object classification codeQ
rated insulation voltage (ui)acc. to IEC/EN 60664-1 1000 V
declaration of conformity - cehttps://library.abb.com/d/1SCC340025D2704
number of auxiliary contacts nc1
number of auxiliary contacts no2
connecting capacity main circuitHole Diameter 10 mmScrew Clamp / PE Terminal 4pc,25 ... 120 mm2
data sheet, technical informationhttps://library.abb.com/d/1SCC340015C0201
maximum mounted auxiliary contacts2 NO, 1 NC
conventional thermal current (ithe)Fully Enclosed 400 A
rated operational power ac-23a (pe)(380 ... 415 V) 220 kW(500 V) 280 kW(690 V) 355 kW
rated operational current ac-22a (ie)(380 ... 415 V) 400 A(500 V) 400 A(690 V) 400 A
rated operational current ac-23a (ie)(380 ... 415 V) 400 A(500 V) 400 A(690 V) 400 A
rated impulse withstand voltage (uimp)12 kV
rated short-circuit making capacity (icm)(1000 V AC) 65 kA
rated conditional short-circuit current (inc)61.5 kA
rated short-time withstand current low voltage (icw)for 1 s 15 kA