Weight | 48.07 KG / psc. |
Commodity number | 85365080 |
Country of origin | FI |
Dimensions (WxHxD) | 480x376x335 mm |
EAN code | 6417019383774 |
Product group | FA |
eclass | V11.1 : 27371403 |
etim 5 | EC000216 - Switch disconnector |
etim 6 | EC000216 - Switch disconnector |
etim 7 | EC000216 - Switch disconnector |
etim 8 | EC000216 - Switch disconnector |
unspsc | 39122233 |
standards | UL 98 / IEC60947-3 |
handle type | Handle and shaft included |
handle color | Black |
mounting type | Base mounting |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
operating mode | Front operated |
number of poles | 4 |
transition type | Open |
fourth pole type | Switched - Simultaneous Function |
pollution degree | 3 |
ampere rating ul/csa | 800 A |
degree of protection | Front IP20 |
fourth pole position | Right Side |
mechanical durability | 3000 cycle |
distance between phases | Standard |
horsepower rating ul/csa | (acc. to UL 240 V) 250 Hp(acc. to UL 480 V) 500 Hp(acc. to UL 600 V) 500 Hp |
environmental information | https://library.abb.com/d/1SCC303050D0201 |
rated operational voltage | 1000 V |
object classification code | Q |
position of line terminals | Top In - Bottom Out, Bottom In - Top Out |
switches operating mechanism | Mechanism at the End of the Switch04 (Left Side) |
declaration of conformity - ce | https://library.abb.com/d/1SCC303014D0201 |
data sheet, technical information | https://library.abb.com/d/1SCC303003C0201 |
rated operational current ac-21a (ie) | (380 ... 415 V) 1600 A(500 V) 1600 A(690 V) 1600 A |
rated operational current ac-22a (ie) | (380 ... 415 V) 1600 A(500 V) 1600 A(690 V) 1600 A |
rated operational current ac-23a (ie) | (380 ... 415 V) 1600 A(500 V) 1600 A(690 V) 1600 A |
rated operational current ac-31b (ie) | (380 ... 415 V) 1600 A |
rated operational current ac-33b (ie) | (380 ... 415 V) 1000 A |
rated impulse withstand voltage (uimp) | 12 kV |
conventional free-air thermal current (ith) | q = 40 °C 1600 A |
rated short-time withstand current low voltage (icw) | for 1 s 50 kiloampere rms |