Weight | 8.1 KG / psc. |
Commodity number | 85365080 |
Country of origin | Finland (FI) |
Dimensions (WxHxD) | 331x150x285 mm |
EAN code | 6417019686486 |
Product group | FA |
eclass | V11.1 : 27371403 |
etim 5 | EC000216 - Switch disconnector |
etim 6 | EC000216 - Switch disconnector |
etim 7 | EC000216 - Switch disconnector |
etim 8 | EC000216 - Switch disconnector |
lock type | Yes |
standards | IEC 60947-3 |
power loss | at Rated Operating Conditions per Pole 6.5 W |
handle type | Direct mounted handle |
rohs status | Following EU Directive 2011/65/EU |
handle color | Black |
mounting type | Base mounting |
terminal type | Lug terminals |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
operating mode | Front operated |
number of poles | 4 |
transition type | Open |
fourth pole type | Switched - Simultaneous Function |
pollution degree | 3 |
tightening torque | acc. IEC 60947-1 15...22 N·m |
degree of protection | Front IP00 |
fourth pole position | Right Side |
mechanical durability | 20000 |
distance between phases | Standard |
motor operational voltage | 220 ... 240 V AC |
rated operational voltage | Main Circuit 1000 V |
object classification code | Q |
position of line terminals | Top In - Bottom Out, Bottom In - Top Out |
switches operating mechanism | Mechanism at the End of the Switch |
rated insulation voltage (ui) | acc. to IEC/EN 60664-1 1000 V |
declaration of conformity - ce | https://library.abb.com/d/No declaration needed |
data sheet, technical information | https://library.abb.com/d/1SCC303003C0201 |
conventional thermal current (ithe) | Fully Enclosed 250 A |
rated operational power ac-23a (pe) | (220 ... 240 V) 75 kW(400 ... 415 V) 140 kW(500 V) 170 kW(690 V) 250 kW |
rated operational current ac-21a (ie) | (380 ... 415 V) 250 A(500 V) 250 A(690 V) 250 A |
rated operational current ac-22a (ie) | (380 ... 415 V) 250 A(500 V) 250 A(690 V) 250 A |
rated operational current ac-23a (ie) | (380 ... 415 V) 250 A(500 V) 250 A(690 V) 250 A |
rated impulse withstand voltage (uimp) | 12 kV |
rated short-circuit making capacity (icm) | (690 V) 30 kA |
conventional free-air thermal current (ith) | q = 40 °C 250 A |
rated short-time withstand current low voltage (icw) | for 1 s 8 kA |