Weight | 4.15 KG / psc. |
Commodity number | 85389099 |
Country of origin | |
Dimensions (WxHxD) | 186x205x103.5 mm |
EAN code | 8015644556914 |
Product group | LA |
device | Breaking Part |
eclass | V11.1 : 27370409 |
etim 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
etim 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
version | F |
sub-type | T5 |
standards | IEC |
rohs status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
product name | Moulded Case Circuit Breaker |
suitable for | T5 |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
gl certificate | https://library.abb.com/d/1SDL000163R0062 |
number of poles | 4 |
rohs information | https://library.abb.com/d/9AKK108466A1424 |
product main type | SACE Tmax T |
reach declaration | https://library.abb.com/d/9AKK108466A1425 |
electrical durability | 5000 cycle60 cycles per hour |
mechanical durability | 20000 cycle120 cycles per hour |
terminal connection type | Fixed Circuit-BreakersFront |
test voltage max (utest) | 3500 V |
environmental information | https://library.abb.com/d/9AKK10103A1056 |
rated operational voltage | 690 V AC750 V DC |
object classification code | Q |
suitable for product class | Moulded Case Circuit Breakers |
rated insulation voltage (ui) | 1000 V |
declaration of conformity - ce | https://library.abb.com/d/9AKK106713A5539 |
short-circuit performance level | S |
rated uninterrupted current (iu) | 630 A |
data sheet, technical information | https://library.abb.com/d/1SDC210004D0203 |
rated impulse withstand voltage (uimp) | 8 kV |
test voltage at industrial frequency for 1 minute | 3500 V |
rated service short-circuit breaking capacity (ics) | (220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 50 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 40 kA(500 V AC) 30 kA(690 V AC) 25 kA |
rated ultimate short-circuit breaking capacity (icu) | (220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 50 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 40 kA(500 V AC) 30 kA(690 V AC) 25 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 2 Poles in Series 36 kA(750 V DC) 3 Poles in Series 25 kA |