Weight | 9.7 KG / psc. |
Commodity number | 85362090 |
Country of origin | |
Dimensions (WxHxD) | 210x268x154 mm |
EAN code | 8015644652548 |
Product group | LA |
eclass | V11.1 : 27370409 |
etim 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
etim 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
unspsc | 39121100 |
release | PR231/P-I |
version | F |
sub-type | T7 |
standards | IEC |
power loss | at Rated Operating Conditions per Pole 32 W |
rohs status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
product name | Moulded Case Circuit Breaker |
release type | EL |
suitable for | T7 |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
gl certificate | https://library.abb.com/d/1SDL000163R0056 |
number of poles | 3 |
rohs information | https://library.abb.com/d/9AKK108466A1424 |
product main type | SACE Tmax T |
reach declaration | https://library.abb.com/d/9AKK108466A1425 |
rated current (in) | Main Circuit 800 A |
electrical durability | 3000 cycle60 cycles per hour |
mechanical durability | 10000 cycle60 cycles per hour |
terminal connection type | Fixed Circuit-BreakersFront |
environmental information | https://library.abb.com/d/9AKK10103A1059 |
rated operational voltage | 690 V AC |
object classification code | Q |
suitable for product class | Moulded Case Circuit Breakers |
rated insulation voltage (ui) | 1000 V |
declaration of conformity - ce | https://library.abb.com/d/9AKK106713A5537 |
short-circuit performance level | V |
rated uninterrupted current (iu) | 800 A |
data sheet, technical information | https://library.abb.com/d/1SDC210015D0201 |
rated impulse withstand voltage (uimp) | 8 kV |
rated service short-circuit breaking capacity (ics) | (220 V AC) 200 kA(230 V AC) 200 kA(380 V AC) 150 kA(400 V AC) 150 kA(415 V AC) 150 kA(440 V AC) 130 kA(500 V AC) 100 kA(690 V AC) 45 kA |
rated short-time withstand current low voltage (icw) | for 1 s 15 kA |
rated ultimate short-circuit breaking capacity (icu) | (220 V AC) 200 kA(230 V AC) 200 kA(380 V AC) 150 kA(400 V AC) 150 kA(415 V AC) 150 kA(440 V AC) 130 kA(500 V AC) 100 kA(690 V AC) 60 kA |