Weight | 11.7 KG / psc. |
Commodity number | 85362090 |
Country of origin | |
Dimensions (WxHxD) | 427x382x282 mm |
EAN code | 8015644687069 |
Product group | LA |
eclass | V11.1 : 27370409 |
etim 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
etim 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
release | PR332/P LSIG |
version | F |
sub-type | T8 |
standards | IEC 60947 |
power loss | at Rated Operating Conditions per Pole 117 W |
rohs status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
product name | Moulded Case Circuit Breaker |
release type | EL |
weee category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
number of poles | 3 |
rohs information | https://library.abb.com/d/9AKK108466A1424 |
product main type | SACE Tmax T |
reach declaration | https://library.abb.com/d/9AKK108466A1425 |
rated current (in) | 3200 A |
electrical durability | 3000 cycle20 cycles per hour |
mechanical durability | 15000 cycle60 cycles per hour |
order code us and canada | T8VFF3JS000000XX |
terminal connection type | Fixed Circuit-BreakersRear flat Vertical |
environmental information | https://library.abb.com/d/9AKK107046A3003 |
rated operational voltage | 690 V AC |
object classification code | Q |
rated insulation voltage (ui) | 1000 V |
declaration of conformity - ce | https://library.abb.com/d/9AKK106713A5533 |
short-circuit performance level | V |
rated uninterrupted current (iu) | 3200 A |
data sheet, technical information | https://library.abb.com/d/1SDC210023D0201 |
rated impulse withstand voltage (uimp) | 8 kV |
rated service short-circuit breaking capacity (ics) | (220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 75 kA(690 V AC) 60 kA |
rated short-time withstand current low voltage (icw) | for 1 s 40 A |
rated ultimate short-circuit breaking capacity (icu) | (220 V AC) 1.3 kA(230 V AC) 1.3 kA(380 V AC) 130 kA(400 V AC) 130 kA(415 V AC) 130 kA(440 V AC) 130 kA(500 V AC) 100 kA(690 V AC) 80 kA |