Weight | 56 KG / psc. |
Commodity number | 85362090 |
Country of origin | |
Dimensions (WxHxD) | 384x371x270 mm |
EAN code | 8015644750701 |
Product group | LA |
eclass | V11.1 : 27370409 |
etim 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
etim 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
etim 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
release | Ekip G Hi-Touch LSIG |
version | F |
sub-type | E4.2 |
standards | IEC |
power loss | 465 W |
rohs status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
current type | AC |
product name | Air Circuit Breaker |
release type | EL |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
number of poles | 3 |
rohs information | https://library.abb.com/d/9AKK108466A1424 |
product main type | SACE Emax 2 |
reach declaration | https://library.abb.com/d/9AKK108466A1425 |
rated current (in) | 4000 A |
rated voltage (ur) | 690 V |
electrical durability | Ue =< 440 V 5000 cycleUe = 500 ... 690 V 4000 cycle20 cycles per hour |
mechanical durability | 15000 cycle60 cycles per hour |
order code us and canada | Z4HWERBQ200A000000XX |
terminal connection type | Rear flat Horizontal |
environmental information | https://library.abb.com/d/9AKK10103A1038 |
rated operational voltage | 690 V AC |
object classification code | Q |
rated insulation voltage (ui) | AC 1000 V |
declaration of conformity - ce | https://library.abb.com/d/9AKK106713A5545 |
short-circuit performance level | H |
rated uninterrupted current (iu) | 4000 A |
data sheet, technical information | https://library.abb.com/d/1SDC200023D0209 |
rated impulse withstand voltage (uimp) | acc. to IEC 60947-2 12 kV |
rated service short-circuit breaking capacity (ics) | (220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(660 V AC) 85 kA(690 V AC) 85 kA |
rated short-time withstand current low voltage (icw) | for 1 s 85 kAfor 3 s 75 kA |
rated ultimate short-circuit breaking capacity (icu) | (400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(525 V AC) 85 kA(690 V AC) 85 kA |
rated service short-circuit breaking capacity, in % of icu (ics) | 100 % |