ABB

1SFL487002R1222

Product type: AF190-30-22-12

AF190-30-22-12 Contactor

Description

The AF190-30-22-12 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 90 kW / 400 V AC (AC-3) or 125 hp / 480 V UL and switching power circuits up to 275 A (AC-1) or 250 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Block Contactors
Contact Person
Thomas Hoffmann
+49 305 201 4443 ext. 1
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: ca. 1-2 Days
Delivery Time: By Agreement
Delivery Terms: FCA Berlin
Infoindividually for each client according to INCOM TERMS 2022
  • ZWOD Vertriebs und Logistik GmbH specializes in hard-to-find parts. Please send request a quote and save on 1SFL487002R1222.
  • ZWOD Vertriebs und Logistik GmbH carries 225191 items from ABB.
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight2.4 KG / psc.
Commodity number85364900
Country of originSE
Dimensions (WxHxD)105x196x152 mm
EAN code7320500480472
Product groupSC
eclassV11.0 : 27371003
etim 4EC000066 - Magnet contactor, AC-switching
etim 5EC000066 - Magnet contactor, AC-switching
etim 6EC000066 - Power contactor, AC switching
etim 7EC000066 - Power contactor, AC switching
etim 8EC000066 - Power contactor, AC switching
unspsc39121529
rohs statusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
operate timeBetween Coil De-energization and NO Contact Opening 37 ... 47 msBetween Coil Energization and NO Contact Closing 25 ... 55 ms
terminal typeMain Circuit: Bars
bv certificatehttps://library.abb.com/d/BV_36353_A0BV
cb certificatehttps://library.abb.com/d/SE-82315
gl certificatehttps://library.abb.com/d/GL_95072-14HH
kc certificatehttps://library.abb.com/d/9AKK107046A9912
lr certificatehttps://library.abb.com/d/LR_14_70011(E1)
abs certificatehttps://library.abb.com/d/14-LD1092198-PDA
ccs certificatehttps://library.abb.com/d/GB14T00030
cqc certificatehttps://library.abb.com/d/CQC2014010304676685, https://library.abb.com/d/CQC2014010304724672
cul certificatehttps://library.abb.com/d/20121023-E36588
dnv certificatehttps://library.abb.com/d/DNV_E-14043
eac certificatehttps://library.abb.com/d/9AKK107046A8618
prs certificatehttps://library.abb.com/d/TE_2092_880423_16
ul listing cardhttps://library.abb.com/d/UL_E36588
coil consumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 4 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 4 V·AHolding at Max. Rated Control Circuit Voltage DC 2.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·APull-in at Max. Rated Control Circuit Voltage DC 150 W
rina certificatehttps://library.abb.com/d/ELE060313XG_002
rmrs certificatehttps://library.abb.com/d/9AKK107045A6978
rohs informationhttps://library.abb.com/d/2CMT2015-005439
dimension diagramhttps://library.abb.com/d/1SFB535001G1056
dnv gl certificatehttps://library.abb.com/d/DNV_E-14043
e-number (finland)3706392
rated frequency (f)Main Circuit 50 / 60 Hz
degree of protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
coil operating limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
mechanical durability5 million
ambient air temperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... +70 °C
horsepower rating ul/csa(200 V AC) Three Phase 50 hp(208 V AC) Three Phase 50 hp(220 ... 240 V AC) Three Phase 60 hp(440 ... 480 V AC) Three Phase 125 hp(550 ... 600 V AC) Three Phase 150 hp
environmental informationhttps://library.abb.com/d/2CMT004732, https://library.abb.com/d/1SAC200042H0004
general use rating ul/csa(600 V AC) 250 A
maximum breaking capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A
rated operational voltageMain Circuit 1000 V
number of main contacts nc0
number of main contacts no3
object classification codeQ
rated making capacity ac-310 x Ie AC-3
rated making capacity ac-3e12 x Ie AC-3e
rated breaking capacity ac-38 x Ie AC-3
rated breaking capacity ac-3e8.5 x Ie AC-3e
rated insulation voltage (ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
declaration of conformity - cehttps://library.abb.com/d/2CMT2015-005439
declaration of conformity - ccchttps://library.abb.com/d/2020980304001306, https://library.abb.com/d/2020980304001071
number of auxiliary contacts nc2
number of auxiliary contacts no2
connecting capacity main circuitFlexible 2 x 50 ... 95 mm2Rigid Al-Cable 1 x 95 ... 185 mm2Rigid Cu-Cable 2 x 50 ... 120 mm2
declaration of conformity - ukcahttps://library.abb.com/d/2CMT2020-006118
maximum operating voltage ul/csaMain Circuit 1000 V
short-circuit protective devicesgG Type Fuses 355 A
data sheet, technical informationhttps://library.abb.com/d/1SBC100192C0206
rated operational power ac-3 (pe)(415 V) 90 kW(440 V) 110 kW(500 V) 90 kW(690 V) 132 kW(1000 V) 110 kW(380 / 400 V) 90 kW(220 / 230 / 240 V) 55 kW
idea granular category code (igcc)4755 >> Contactors
rated control circuit voltage (uc)50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
rated operational power ac-3e (pe)(415 V) 90 kW(440 V) 110 kW(500 V) 90 kW(690 V) 132 kW(1000 V) 110 kW(380 / 400 V) 90 kW(220 / 230 / 240 V) 55 kW
rated operational current ac-1 (ie)(1000 V) 40 °C 250 A(1000 V) 55 °C 225 A(1000 V) 60 °C 225 A(1000 V) 70 °C 185 A(690 V) 40 °C 275 A(690 V) 55 °C 250 A(690 V) 60 °C 250 A(690 V) 70 °C 200 A
rated operational current ac-3 (ie)(415 V) 55 °C 190 A(440 V) 55 °C 190 A(500 V) 55 °C 156 A(690 V) 55 °C 135 A(1000 V) 55 °C 85 A(380 / 400 V) 55 °C 190 A(220 / 230 / 240 V) 55 °C 190
rated operational current dc-1 (ie)(110 V) 2 Poles in Series, 40 °C 250 A(220 V) 3 Poles in Series, 40 °C 250 A
rated operational current dc-3 (ie)(110 V) 2 Poles in Series, 40 °C 250 A(220 V) 3 Poles in Series, 40 °C 250 A
rated operational current dc-5 (ie)(110 V) 2 Poles in Series, 40 °C 250 A(220 V) 3 Poles in Series, 40 °C 250 A
rated operational current ac-3e (ie)(415 V) 60 °C 190 A(440 V) 60 °C 190 A(500 V) 60 °C 135 A(690 V) 60 °C 135 A(1000 V) 60 °C 85 A(380 / 400 V) 60 °C 190 A(220 / 230 / 240 V) 60 °C 190 A
connecting capacity auxiliary circuitFlexible with Ferrule 2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Flexible 2x0.75 ... 2.5 mm2Solid 2 x 1 ... 4 mm2Stranded 2 x 1 .... 4 mm2
maximum electrical switching frequency(AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
maximum mechanical switching frequency300 cycles per hour
maximum operating altitude permissibleWithout Derating 3000 m
rated impulse withstand voltage (uimp)Main Circuit 8 kV
conventional free-air thermal current (ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 275 A
rated short-time withstand current low voltage (icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A

We use cookies

This website collects cookies to deliver better user experience. By using our website, you agree to the use of cookies.

Find out how we use cookies.

We’re sorry, our website no longer supports