Weight | 0.147 KG / psc. |
Commodity number | 85364900 |
Country of origin | DE |
Dimensions (WxHxD) | 22.5x85.6x103.7 mm |
EAN code | 4013614502835 |
Product group | EA |
eclass | V11.0 : 27371813 |
etim 5 | EC001447 - (Fill) level monitoring relay |
etim 6 | EC001447 - (Fill) level monitoring relay |
etim 7 | EC001447 - (Fill) level monitoring relay |
etim 8 | EC001447 - (Fill) level monitoring relay |
output | 1 c/o (SPDT) contact |
function | Filling or draining monitoring |
standards | CAN/CSA C22.2 No.14IEC/EN 63000IEC/EN 60255-27IEC/EN 61000-6-2IEC/EN 61000-6-3UL 508 |
rohs status | Following EU Directive 2011/65/EU |
terminal type | Screwless Terminals |
cqc certificate | https://library.abb.com/d/CQC2015010303819793 |
eac certificate | https://library.abb.com/d/EAC_RU_C-DE.ME77.B.02330 |
measuring range | 01 ... 1000 kΩ |
pollution degree | 3 |
rohs information | https://library.abb.com/d/1SVD981005-00 |
culus certificate | https://library.abb.com/d/cULus508_20150627-E140448 |
mounting position | 1 ... 5; 1 ... 6 |
pilot duty ul/csa | B300 |
tightening torque | Control Circuit 0.9 N·mMain Circuit 1 N·m |
dnv gl certificate | https://library.abb.com/d/DNV_GL_TAA00000RW |
e-number (finland) | 2712575 |
connecting capacity | Flexible with Ferrule 2x 0.5 ... 1.5 mm2Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm2Flexible 2x 0.5 ... 1.5 mm2Rigid 2x 0.5 ... 1.5 mm2 |
rated frequency (f) | Supply Circuit 50/60 Hz |
degree of protection | Housing IP50Terminals IP20 |
mounting on din rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
number of electrodes | 3 |
overvoltage category | III |
contact rating ul/csa | B300 |
electrical durability | AC-12 100000 cycle |
mechanical durability | 1000000 cycle |
wire stripping length | 8 mmMain Circuit 10 mm |
ambient air temperature | Operation -25 ... +60 °CStorage -40 ... +85 °C |
connecting capacity ul/csa | Flexible 2x 18-16 AWGRigid 2x 20-16 AWG |
minimum switching capacity | 12 V10 mA |
object classification code | B |
rated insulation voltage (ui) | Measuring Circuit / Output Circuit 300 VOutput Circuit 1 / Output Circuit 2 300 VSupply Circuit / Measuring Circuit 300 VSupply Circuit / Output Circuit 300 V |
declaration of conformity - ce | https://library.abb.com/d/1SVD981005-00 |
declaration of conformity - ccc | https://library.abb.com/d/2020980303000198 |
declaration of conformity - ukca | https://library.abb.com/d/1SVD981005-10 |
maximum operating voltage ul/csa | Output Circuit 300 V AC |
short-circuit protective devices | Output Circuit NC - F Type Fuses 6 AOutput Circuit NO - F Type Fuses 10 A |
data sheet, technical information | https://library.abb.com/d/2CDC112229D0201 |
rated control supply voltage (us) | 110 ... 130 V AC220 ... 240 V AC |
rated operational current ac-12 (ie) | (230 V) 4 A |
rated operational current ac-15 (ie) | (230 V) 3 A |
rated operational current dc-12 (ie) | (24 V) 4 A |
rated operational current dc-13 (ie) | (24 V) 2 A |
maximum operating altitude permissible | Without Derating 2000 m |
rated impulse withstand voltage (uimp) | Measuring Circuit / Output Circuit 4 kVOutput Circuit 1 / Output Circuit 2 4 kVSupply Circuit / Measuring Circuit 4 kVSupply Circuit / Output Circuit 4 kV |