Weight | 980 G / psc. |
Commodity number | 85362090 |
Country of origin | Switzerland (CH) |
Dimensions (WxHxD) | 106x142x82.5 mm |
EAN code | 7612271420796 |
Product group | AF |
cn8 | 85362020 |
eclass | V11.0 : 27141901 |
etim 7 | EC000042 - Miniature circuit breaker (MCB) |
etim 8 | EC000042 - Miniature circuit breaker (MCB) |
standards | UL 489 |
power loss | 6 Wat Rated Operating Conditions per Pole 1.5 W |
rohs status | Following EU Directive 2011/65/EU |
release type | Other |
frequency (f) | 0...0 Hz |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
weee b2c / b2b | Business To Business |
number of poles | 4 |
actuator marking | I / O |
options provided | Universal current |
pollution degree | 3 |
rohs information | https://library.abb.com/d/2CCC413009D0201, https://library.abb.com/d/9AKK107680A3903 |
eplan catalog tree | Electrical engineering / Protection devices / General |
input voltage type | DC |
product net length | 106 mm |
rated current (in) | 80 A |
rated voltage (ur) | acc. to UL489B 600 V DC |
ambient temperature | -25...60 °C |
built-in depth (t2) | 82.5 mm |
connecting capacity | Flexible 0...50 mm2Rigid 0...70 mm2 |
rated frequency (f) | 0 ... 0 Hz |
degree of protection | IP20 |
overvoltage category | III |
accessories available | Yes |
energy limiting class | 3 |
ambient air temperature | Operation -25...60 °C |
tripping characteristic | Z |
environmental information | https://library.abb.com/d/2CCY413207D0203 |
number of protected poles | 4 |
rated operational voltage | 600 V DC |
object classification code | F |
contact position indication | ON / OFF / TRIP |
rated short-circuit capacity | (400 V) 10 kA(230 V) 10 kA |
rated insulation voltage (ui) | acc. to IEC/EN 60664-1 1500 V |
declaration of conformity - ce | https://library.abb.com/d/2CCC413009D0201 |
rated operational current (ie) | 80 A |
data sheet, technical information | https://library.abb.com/d/2CCC413003C0208 |
interrupting rating acc. to ul489 | (600 V DC) 10 kA |
width in number of modular spacings | 6 |
rated impulse withstand voltage (uimp) | 8 kV |
rated conditional short-circuit current (inc) | (230 V) 10 kA(400 V) 10 kA |
rated ultimate short-circuit breaking capacity (icu) | (230 V) 10 kA(400 V) 10 kA |