ABB

2CCS572001R1254

Product type: S402M-UCC25

S402M-UCC25 Miniature Circuit Breaker

Description

The miniature circuit breaker S400M UC extends the establishedSMISSLINE TP product range with an MCB for DC and AC applications. The S400M UC impresses with its performance range. Its high inbuilt short circuit breaking capacity across the entire model line, its flexible AC and DC application. MCBs of the product range S400M UC are comply with IEC/EN 60947-2. The pluggable solution is only for the SMISSLINE TP System, allowing the use for commercial, industrial, and critical power applications. It is also the perfect fit for any application where costly downtime must be avoided.
  • Low Voltage Products and Systems
  • Modular DIN Rail Products
  • Plug-in Distribution Systems
  • Miniature Circuit Breakers MCBs
Contact Person
Thomas Hoffmann
+49 305 201 4443 ext. 1
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: ca. 1-2 Days
Delivery Time: By Agreement
Delivery Terms: FCA Berlin
Infoindividually for each client according to INCOM TERMS 2022
  • ZWOD Vertriebs und Logistik GmbH specializes in hard-to-find parts. Please send request a quote and save on 2CCS572001R1254.
  • ZWOD Vertriebs und Logistik GmbH carries 225191 items from ABB.
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight290 G / psc.
Commodity number85363000
Country of originSwitzerland (CH)
Dimensions (WxHxD)36x91x75 mm
EAN code7612270110032
Product groupAF
cn885363020
size2 modules
eclassV11.0 : 27141901
etim 7EC000042 - Miniature circuit breaker (MCB)
etim 8EC000042 - Miniature circuit breaker (MCB)
standardsIEC/EN 60947-2
power loss5.4 W
trip classUC-C
rohs statusFollowing EU Directive 2002/95/EC August 18, 2005 and amendment
release typeC
frequency (f)50 ... 60 Hz
terminal typeScrew Terminals
weee category5. Small Equipment (No External Dimension More Than 50 cm)
weee b2c / b2bBusiness To Business
number of poles2
actuator markingI / O
pollution degree2
rohs informationhttps://library.abb.com/d/2CCC413008D0206_RoHS
dimension diagramhttps://library.abb.com/d/9AKK107492A6192
mounting positionAny
tightening torque2.8 N·m
eplan catalog treeElectrical engineering / Protection devices / General
input voltage typeAC/DC
product net length75 mm
rated current (in)25 A
rated voltage (ur)440 V DC
ambient temperature-25...55 °C
built-in depth (t2)75 mm
connecting capacityFlexible with Ferrule 0.75 ... 25 mm2Flexible 0.75 ... 25 mm2Rigid 0.75 ... 35 mm2Stranded 0.75 ... 35 mm2
rated frequency (f)50 ... 60 Hz
screw terminal typeFailsafe Bi-directional Cylinder-lift Terminal
degree of protectionIP20
electrical endurance10000 cycle
mechanical endurance10000 cycle
overvoltage categoryIII
accessories availableYes
energy limiting class3
e-number (switzerland)809551107
ambient air temperatureOperation -25 ... +60 °CStorage -40 ... +70 °C
power supply connectionArbitrary
tripping characteristicUC-C
recommended screw driverPozidriv 2
environmental informationhttps://library.abb.com/d/2CCY000200D0231
number of protected poles2
rated operational voltageacc. to IEC 60947-2 440 V DC
object classification codeFC
contact position indicationRed ON / Green OFF
rated short-circuit capacity(400 V) 10 kA(230 V) 10 kA
rated insulation voltage (ui)acc. to IEC/EN 60664-1 440 V
declaration of conformity - cehttps://library.abb.com/d/9AKK107991A9644
data sheet, technical informationhttps://library.abb.com/d/9AKK107492A6192
reference ambient air temperature30 °C
width in number of modular spacings2
rated impulse withstand voltage (uimp)4 kV
rated conditional short-circuit current (inc)(400 V) 10 kA(230 V) 25 kA
resistance to vibrations acc. to iec 60068-2-62...13.2 Hz/1 mm13.2...100Hz/0.7 g, 5 cycles5...150 ... 5 Hz/1 g, 4 waves
rated service short-circuit breaking capacity (ics)(400 V AC) 7.5 kA
rated ultimate short-circuit breaking capacity (icu)(440 V DC) 25 kA(230 V) 25 kA(400 V) 10 kA
rated service short-circuit breaking capacity, in % of icu (ics)50 %