Weight | 0.15 KG / psc. |
Commodity number | 85362010 |
Country of origin | Germany (DE) |
Dimensions (WxHxD) | 17.5x85x69 mm |
EAN code | 4016779826143 |
Product group | AB |
cn8 | 8536 20 10 |
eclass | V11.0 : 27141901 |
etim 7 | EC000042 - Miniature circuit breaker (MCB) |
etim 8 | EC000042 - Miniature circuit breaker (MCB) |
unspsc | 39121614 |
remarks | Please note polarity of device |
standards | UL 489 |
power loss | 2.8 Wat Rated Operating Conditions per Pole 2.8 W |
rohs status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
terminal type | Double Clamp |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
weee b2c / b2b | Business To Business |
number of poles | 1 |
pole net weight | 0.14 kg |
actuator marking | I / O |
housing material | Insulation Group I, RAL 7035 |
pollution degree | 3 |
rohs information | https://library.abb.com/d/2CDK400630D2702 |
actuator material | Insulation Group II, Black, Sealable |
installation size | acc. to DIN 43880 2 |
mounting position | Any |
tightening torque | 2.8 N·m |
eplan catalog tree | Electrical engineering / Protection devices / General |
input voltage type | DC |
rated current (in) | 1.6 A |
built-in depth (t2) | 69 mm |
connecting capacity | Busbar 10 / 10 mm2Flexible with Ferrule 0.75 ... 16 mm2Flexible 0.75 ... 16 mm2Rigid 0.75 ... 25 mm2Stranded 0.75 ... 25 mm2 |
rated frequency (f) | DC |
screw terminal type | Failsafe Bi-directional Cylinder-lift Terminal |
certification agency | UL |
degree of protection | IP20Enclosure with Cover IP40 |
mechanical endurance | 20000 cycle |
mounting on din rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
overvoltage category | III |
accessories available | Yes |
energy limiting class | 3 |
ambient air temperature | Operation -25 ... +55 °CStorage -40 ... +70 °C |
power supply connection | Please Note Polarity of Device |
tripping characteristic | Z |
environmental conditions | 28 cycleswith 55 °C / 90-96 %and 25 °C / 95-100 % |
recommended screw driver | Pozidriv 2 |
tightening torque ul/csa | 25 in·lb |
environmental information | https://library.abb.com/d/9AKK107680A6947 |
eplan function definition | Circuit breaker / Single circuit breaker / Circuit breaker 1_2 |
number of protected poles | 1 |
rated operational voltage | 60 V DCacc. to IEC 60947-2 60 V |
connecting capacity ul/csa | Busbar 18-8 AWGConductor 18-4 AWG |
object classification code | F |
contact position indication | Red ON / Green OFF |
rated short-circuit capacity | (230 V AC) 14 kA |
rated insulation voltage (ui) | 440 Vacc. to IEC/EN 60664-1 440 V |
declaration of conformity - ce | https://library.abb.com/d/2CDK400630D2702 |
maximum operating voltage ul/csa | 125 V DC |
data sheet, technical information | https://library.abb.com/d/No document needed |
interrupting rating acc. to ul489 | (125 V DC) 14 kA(60 V DC) 14 kA |
width in number of modular spacings | 1 |
rated impulse withstand voltage (uimp) | 4 kVat 2000 m 5 kVat Sea Level 6.2 kV |
resistance to shock acc. to iec 60068-2-27 | 30g / 3 shocks / 11 ms |
resistance to vibrations acc. to iec 60068-2-6 | 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In |
rated service short-circuit breaking capacity (ics) | (230 V AC) 14 kA |