Weight | 0.12 KG / psc. |
Commodity number | 85363090 |
Country of origin | Bulgaria (BG) |
Dimensions (WxHxD) | 17.8x95x58 mm |
EAN code | 3660308519573 |
Product group | AK |
cn8 | 85363090 |
eclass | V11.0 : 27130805 |
etim 7 | EC000941 - Surge protection device for power supply systems |
etim 8 | EC000941 - Surge protection device for power supply systems |
version | Plug-in |
fuse size | 1 modular spacing |
standards | IEC 61643-11 / EN 61643-11 |
power loss | 8 mW |
declaration | https://library.abb.com/d/2CTC432056G1701 |
suitable for | To protect the systems against the transient overvoltage (lightning) |
mounting type | DIN rail (top hat rail) 35 mm |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
arrester class | IIIII |
cb certificate | https://library.abb.com/d/2CTC432057G1701 |
weee b2c / b2b | Business To Consumer |
cqc certificate | https://library.abb.com/d/9AKK107680A1974 |
impulse current | I (imp, 10 / 350 μs) 2 kA |
number of poles | 1 |
options provided | Residential or other where accurate protection is needed. |
status indicator | Yes |
discharge current | Nominal 5 kAMaximum 20 kATotal 20 kANominal (8 / 20 μs) 5 kAI (max, 8 / 20 μs) 20 kA |
voltage rating dc | 350 V |
rated voltage (ur) | 400 V AC |
mechanical drawings | https://library.abb.com/d/2CTC800021F0200.pdf, https://library.abb.com/d/2CTC800021F0201.dxf, https://library.abb.com/d/2CTC800021F0202.stp, https://library.abb.com/d/2CTC800021F0203.igs |
degree of protection | IP20 |
number of conductors | 1 |
transmission standard | Optic |
auxiliary circuit load | Minimum 12Vdc - 10mAMaximum 250Vac - 1A |
number of protected poles | 1 |
object classification code | 141ECC |
short circuit withstand icc | 100 kA |
declaration of conformity - ce | https://library.abb.com/d/9AKK108466A4410 |
preventive maintenance feature | No |
voltage protection level ( up) | 1 kV(L-N) - kV(N-PE) - kV(L-PE) 0.9 kV |
number of auxiliary contacts nc | 1 |
number of auxiliary contacts no | 1 |
short-circuit protective devices | Curve B Breakers ≤ 125 ACurve C Breakers ≤ 125 AgL Type Fuses ≤ 125 AgG Type Fuses ≤ 125 A |
data sheet, technical information | https://library.abb.com/d/2CTC432207D0201 |
width in number of modular spacings | 1 |
nominal ac voltage of the system (uo) | 230 / 400 V |
temporary overvoltage test value (ut) | 337 V |
maximum operating altitude permissible | Without Derating 5000 |
type of low voltage distribution system | TTTN-CTN-S |
maximum continuous operating voltage (uc) | (L-PE) 275 V(L-L) 275 V(L-N) 275 V(N-PE) - V |
rated service short-circuit breaking capacity (ics) | 100 kA |