Weight | 0.3 KG / psc. |
Commodity number | 85363090 |
Country of origin | Bulgaria (BG) |
Dimensions (WxHxD) | 35.6x88x76.7 mm |
EAN code | 3660308524966 |
Product group | AK |
cn8 | 85363090 |
eclass | V11.0 : 27130808 |
etim 7 | EC001457 - Combined arrester for power supply systems |
etim 8 | EC001457 - Combined arrester for power supply systems |
version | Plug-in |
fuse size | 2 modular spacing |
standards | IEC 61643-11 / EN 61643-11 |
power loss | 37 mW |
declaration | https://library.abb.com/d/2CTC432056G1701 |
rohs status | Following EU Directive 2011/65/EU |
suitable for | To protect the systems against the transient overvoltage (lightning) |
mounting type | DIN rail (top hat rail) 35 mm |
weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
arrester class | III |
weee b2c / b2b | Business To Business |
cqc certificate | https://library.abb.com/d/9AKK107680A1975 |
eac certificate | https://library.abb.com/d/2CTC436008G1701 |
impulse current | I (imp, 10 / 350 μs) 12.5 kAI (total, 10 / 350 μs) 25 kA |
number of poles | 2 |
options provided | Industry, commercial building |
rohs information | https://library.abb.com/d/9AKK108466A4617 |
status indicator | Yes |
discharge current | Nominal 20 kAMaximum 80 kATotal 100 kA |
voltage rating dc | 350 V |
mechanical drawings | https://library.abb.com/d/2CTC800015F1600.pdf, https://library.abb.com/d/2CTC800015F1601.dxf, https://library.abb.com/d/2CTC800015F1602.stp, https://library.abb.com/d/2CTC800015F1603.igs |
degree of protection | IP20 |
lightning impulse current | 12,5 |
number of protected poles | 2 |
object classification code | 141BCC |
short circuit withstand icc | 100 kA |
position of neutral terminals | Right |
declaration of conformity - ce | https://library.abb.com/d/9AKK108466A4617 |
preventive maintenance feature | Yes |
voltage protection level ( up) | (L-N) 1.4 kV(N-PE) 1.4 kV(L-PE) 1.5 kV |
short-circuit protective devices | Curve B Breakers ≤ 125 ACurve C Breakers ≤ 125 AgL Type Fuses ≤ 160 AgG Type Fuses ≤ 160 A |
data sheet, technical information | https://library.abb.com/d/2CTC431043D0201 |
width in number of modular spacings | 2 |
nominal ac voltage of the system (uo) | 230 / 400 V |
temporary overvoltage test value (ut) | (L-N) 337 V(N-PE) 1200 V |
maximum operating altitude permissible | Without Derating 5000 |
type of low voltage distribution system | TTTN-S |
maximum continuous operating voltage (uc) | (L-PE) 275 V(L-L) - V(L-N) 275 V(N-PE) 255 V |
follow current extinction capacity if (i fi) | (L-N) - kA(N-PE) 0.1 kA |