MULTIVERT NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT main incomers 1000A are for installation on to 185mm bus bar systems. They are ready fitted with solild links 1000A. The system is a modular system, that allows the installation of individual components. MULTIVERT offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance. MULTIVERT 1000A NH fuse-switch disconnector according to IEC / EN 60 947-3, 3-pole switchable infeed bar with multiple connection M12 for cable connection of large cross-sections and permanently mounted disconnecting knives 1000A, installation on 185mm busbar system, symmetrical switch bar - cable outlet above / below at Installation selectable, with installed cable cover, line connection variants: Al / Cu max. 300mm² rm, sm (2 cable lugs) or Cu max. 150mm² rm, sm (3 cable lugs) M = 35 +/- 3Nm.