Transmitter supply unit | Ex i field circuit | explosion-protected | Type : 9160/15-11-10s | Max. voltage Uo : 15,5 V | Max. current Io : 98 mA | Max. power Po : 356 mW | Max. voltage Ui : 30 V | Max. current Ii : 100 mA | Nominal current : 75 mA | Power consumption : 1,8 W | Number of channels : 1 | Connection type : Screw terminal | Input : 0/4 - 20 mA low voltage | Output A : 0/4 to 20 mA | LFD relay : No | SIL : 2 | min. ambient temperature : -20 °C | max. ambient temperature : +70 °C | Application range (zones) : 2 | Gas explosion protection : II 3 (1) G Ex nA [ia Ga] IIC T4 Gc | Dust explosion protection : II (1) D [Ex ia Da] | For further information, see : r-stahl.com WebCode 9160A